Home > Automatic Faucet Set | Sensor Detection Zone

Fontana Touchless Fixtures™ | Architectural and Engineering Resource

Fontana Countertop Faucet & Soap Dispenser: Sensor Detection Zone

This sensor-detection resource is intended to support architects, plumbing engineers, electrical designers, contractors, installers, commissioning personnel and facility managers coordinating the Fontana countertop touchless faucet and automatic soap dispenser within commercial and residential lavatory environments. The drawing identifies the active infrared sensing fields, recommended activation distances, detection angles, optimal hand positions, false-activation conditions and under-counter service clearances.

Fontana Touchless Faucet and Automatic Soap Dispenser Sensor System

This coordinated touchless fixture set uses active infrared reflective sensors to detect a user's hands within defined sensing zones. The faucet and soap dispenser use different recommended operating ranges, while both provide an approximate 40° detection cone. The drawing supports sensor alignment, range adjustment, user-positioning guidance and commissioning.

  • Fixture set: Countertop touchless faucet and automatic soap dispenser
  • Sensor technology: Active infrared reflective sensing
  • Faucet operating range: 50–200 mm (2–8 in.)
  • Soap-dispenser operating range: 30–120 mm (1-1/4–4-3/4 in.)
  • Detection angle: Approximately 40°
  • Response time: Less than 0.5 second
  • Operating voltage: 6–12 VDC
  • Operating temperature: 1–55 °C (34–131 °F)
  • Sensor orientation: Front / downward facing
  • Environment: Indoor use only
  • Vertical service clearance: 300 mm (11-13/16 in.) minimum
  • Horizontal service clearance: 400 mm (15-3/4 in.) minimum

Required Sensor Detection Drawing Package

Each drawing should use a consistent sensing-field graphic, dimension style and sensor identification block. The package should clearly distinguish the faucet and soap-dispenser activation zones, detection angles, recommended operating ranges, hand-positioning guidance and known false-activation conditions. Sensor orientation and adjustment requirements should be documented for installation, testing and commissioning.

Sensor Detection Overview

Shows the faucet and soap-dispenser sensing fields, recommended operating ranges, hand-positioning examples, false-activation zones and installation clearances. This drawing provides an overall reference for sensor coordination and commissioning.

Faucet Sensing Field

Illustrates the faucet detection zone in side and top views. The recommended operating distance extends from 50 mm to 200 mm, with an approximate 40° detection cone centered beneath the outlet.

Soap-Dispenser Sensing Field

Illustrates the dispenser detection zone in side and top views. The recommended activation distance extends from 30 mm to 120 mm, creating a compact sensing area beneath the soap nozzle.

Detection Angle

Identifies the nominal 40° sensing cone for both fixtures. The sensor window should be directed toward the primary hand-approach area and kept clear of nearby obstructions.

Optimal Hand Position

Shows hands placed naturally within the recommended sensing range. Consistent activation is achieved when the user's hands enter the center of the detection field rather than approaching from the side.

Too-Close Condition

Illustrates hand placement inside the minimum activation distance. Positioning too close to the sensor may reduce detection consistency or place the hand outside the sensor's intended reflective field.

Too-Far and Side-Approach Conditions

Shows hand positions beyond the recommended range or entering from the side. These approaches may produce delayed, intermittent or unreliable activation.

False-Activation Zones

Identifies reflective surfaces, direct sunlight and continuous movement as potential causes of unintended activation. Installation should minimize exposure to these environmental conditions.

Range Adjustment and Testing

Coordinates sensor testing after installation and adjustment through the controller where supported. Final settings should provide reliable activation without extending unnecessarily into surrounding traffic areas.

Engineering note: The sensor diagram is a coordination reference and should not be scaled. Keep each sensor window clean, dry and unobstructed. Verify sensing range, detection angle, controller settings, environmental conditions and service clearances against the current product specification and installation instructions before final commissioning.

Sensor Installation and Commissioning Considerations

Sensor Alignment

Align each sensor toward the primary user approach so hands naturally enter the center of the intended sensing field.

Reflective Surfaces

Avoid positioning the sensor directly toward mirrors, glossy panels or other highly reflective surfaces that may return unwanted infrared signals.

Direct Sunlight

Limit direct sunlight on the sensor window because intense external light may interfere with reflective infrared detection.

Obstruction Control

Keep the sensor window and detection cone clear of accessories, splash guards, countertop objects and permanent obstructions.

Range Verification

Test activation at the minimum, midpoint and maximum recommended distances and adjust the controller only where required.

Service Access

Maintain the recommended under-counter clearance for access to the controller, power supply, sensor wiring and adjustment controls.

Professional Engineering and Accessibility References

Project verification: Sensor detection drawings are coordination and commissioning tools and do not replace approved project submittals. The electrical designer, plumbing engineer, contractor and qualified installer should verify sensor orientation, activation range, detection angle, controller settings, environmental conditions, hand approach, service access, accessibility criteria and manufacturer requirements before installation and final commissioning.