Fontana DSFD0024GS Vessel Sink and Chrome Touchless Sensor Faucet: ADA Coordination Drawing

This accessibility-focused coordination resource is intended to support architects, plumbing engineers, interior designers, contractors, accessibility consultants and installers coordinating the Fontana DSFD0024GS vessel sink and chrome touchless sensor faucet combination. The drawing package communicates vessel-sink placement, faucet reach, touchless sensor use zone, forward approach, clear floor space, knee clearance, toe clearance, counter height and under-counter plumbing coordination for accessible use.

Fontana DSFD0024GS Accessible Vessel Sink & Touchless Faucet Coordination

The DSFD0024GS accessibility drawing coordinates the white oval vessel sink, chrome touchless faucet, user approach and under-counter clearances as a complete installation. The faucet centerline, sensor-use area, basin position, clear floor space and protected plumbing are shown together so accessibility and serviceability can be reviewed before fabrication and final installation.

  • Model: DSFD0024GS
  • Basin shape: Oval
  • Basin size: 600 × 420 × 150 mm (23.6 × 16.5 × 5.9 in.)
  • Faucet type: Deck-mount touchless sensor faucet
  • Operation: Touchless motion detection
  • Power supply: AC 110 V / DC 6 V
  • Spout projection: 182 mm (7.17 in.)
  • Spout height above countertop: 200 mm (8 in.)
  • Maximum counter / rim height: 34 in. (865 mm) AFF
  • Minimum knee clearance: 27 in. (685 mm)
  • Minimum toe clearance: 9 in. (230 mm)
  • Typical clear depth: 17–25 in. (430–635 mm)
  • Minimum clear width: 30 in. (760 mm)
  • Forward-approach clear floor space: 30 × 48 in. (760 × 1220 mm)
  • Sensor-use zone: Beneath the spout

Required ADA & Accessibility Coordination Drawing Package

Each accessibility coordination drawing should use a consistent finished-floor datum, faucet centerline, basin centerline and clear floor-space reference. The package should clearly identify counter height, faucet reach, sensor-use zone, forward approach, knee clearance, toe clearance, clear width, protected plumbing and under-counter equipment placement before final installation.

ADA Coordination Drawing

Provides the complete relationship between the vessel sink, touchless faucet, sensor-use zone, forward approach, clear floor space, counter height and under-counter clearance.

Side Elevation — Accessible Use Zone

Shows the seated user relationship to the basin, faucet, sensor zone, 34-inch maximum counter / rim height, 27-inch knee clearance and 9-inch toe clearance.

Faucet Reach & Sensor Zone

Shows the approximately 182 mm (7.17 in.) spout projection, 200 mm (8 in.) spout height and touchless sensing area beneath the spout for comfortable hand entry.

Front Elevation — Clearance Coordination

Identifies the minimum 30-inch (760 mm) clear width beneath the lavatory and the faucet centerline aligned with the vessel sink.

Knee Clearance

Shows a minimum knee-clearance height of approximately 27 inches (685 mm) beneath the countertop for forward wheelchair approach.

Toe Clearance

Shows a minimum toe-clearance height of approximately 9 inches (230 mm) coordinated with the required clear depth under the lavatory.

Plan View — Clear Floor Space

Illustrates the minimum 30 × 48 inch (760 × 1220 mm) clear floor-space area centered on the lavatory for forward approach.

Sensor Reach & Approach

Shows the user hand entering the touchless sensor field without requiring grasping, pinching or twisting of a manual control.

Protected Plumbing Coordination

Identifies supply and drain piping within the accessible under-counter zone and indicates that exposed plumbing should be insulated or otherwise protected where required.

Engineering note: The dimensions shown are coordination references from the illustrated DSFD0024GS accessibility drawing. Final counter height, clear floor space, knee and toe clearance, plumbing protection, faucet reach, sensor location and accessible-route requirements should be verified against the actual installation, approved project documents and applicable accessibility requirements before final installation.

Accessible Use & Fixture Coordination Considerations

Counter / Rim Height

Coordinate the installed countertop and vessel-sink rim so the accessible-use height shown in the drawing is maintained after all finished surfaces are installed.

Forward Approach

Keep the floor area in front of the lavatory clear so the user can approach the sink directly from the front without fixed obstructions.

Knee Space

Keep cabinet framing, controllers, hoses and other components out of the required knee-clearance envelope wherever practical.

Toe Space

Maintain the required toe-clearance zone beneath the lavatory and avoid placing fixed plumbing or millwork within the user's foot area.

Touchless Sensor Reach

Position the faucet so the user can comfortably place a hand within the sensing field without excessive forward reach over the vessel rim.

Faucet & Basin Alignment

Align the faucet and basin centerlines to keep the water stream and sensor-use zone within the most accessible portion of the vessel.

Knee, Toe & Clear Floor Space Coordination

30-Inch Clear Width

Maintain at least the illustrated 30-inch (760 mm) clear width beneath and in front of the lavatory where required by the project.

48-Inch Forward Approach

Keep the illustrated 48-inch (1220 mm) forward-approach depth unobstructed so a wheelchair user can position directly in front of the fixture.

27-Inch Knee Height

Maintain the illustrated minimum 27-inch (685 mm) knee-clearance height beneath the accessible lavatory.

9-Inch Toe Height

Keep the illustrated minimum 9-inch (230 mm) toe-clearance zone open beneath the front portion of the lavatory.

Clear Depth

Coordinate the illustrated 17–25 inch (430–635 mm) clear-depth range with plumbing, cabinetry and structural supports beneath the sink.

Unobstructed Floor Area

Avoid fixed accessories, waste bins, cabinetry or other items within the required clear floor-space envelope.

Under-Counter Plumbing & Equipment Coordination

Protected Supply Piping

Protect exposed hot-water supply piping within the accessible knee space as indicated by the project requirements.

Protected Drain Piping

Coordinate and protect drain piping so the trap and tailpiece do not create an obstruction or contact hazard within the accessible use zone.

Control Module Placement

Locate electronic control modules outside the required knee and toe clearance where practical while maintaining accessible service space.

Hose Routing

Route hot and cold supply hoses so they do not project unnecessarily into the accessible knee-space envelope.

Trap Coordination

Coordinate the trap and wall-drain connection with the clearance envelope before closing walls or installing permanent cabinetry.

Service Access

Maintain access to plumbing and electronic components without compromising the required user clearance beneath the lavatory.

Touchless Sensor & User Operation Coordination

Sensor Use Zone

Keep the touchless sensing zone directly beneath the spout and within comfortable reach from the illustrated forward approach position.

Hands-Free Operation

The electronic sensor arrangement allows water activation without requiring manual grasping, pinching or twisting of a conventional faucet control.

Spout Projection

Coordinate the approximately 182 mm (7.17 in.) spout projection with the vessel rim and user approach so the water outlet remains comfortably reachable.

Water Landing Zone

Keep the faucet outlet aligned with the usable center of the vessel so the stream remains inside the bowl during accessible use.

Sensor Commissioning

After installation, verify the sensor detects a user's hand from the intended accessible approach without excessive reaching.

Clear Approach

Avoid soap dispensers, accessories or fixed objects that interfere with the user's forward reach toward the touchless sensing zone.

Accessibility Installation Best Practices

Verify Finished Height

Check actual finished-floor, countertop and vessel-rim elevations before final fixture installation.

Maintain Clear Floor Space

Keep the illustrated forward-approach zone free from fixed cabinets, accessories and storage items.

Protect Plumbing

Insulate or otherwise protect exposed water-supply and drain components within the user clearance zone as required.

Keep Equipment Outside Knee Space

Coordinate controllers, power components, hoses and service access so they do not unnecessarily reduce the required knee or toe clearances.

Verify Sensor Reach

Test sensor response from the intended user position and confirm operation without excessive reach or awkward hand placement.

Field Verification

Confirm all clearances, heights and access conditions in the field before project handover.

Professional Accessibility and Plumbing References

Project verification: ADA and accessibility coordination drawings are design tools and do not replace approved project documents, governing accessibility standards or manufacturer instructions. The architect, accessibility consultant, plumbing engineer, contractor and licensed installer should verify counter / rim height, clear floor space, knee and toe clearance, faucet reach, sensor operation, plumbing protection, control-module location, accessible route and all applicable project requirements before final installation and commissioning.